GENERAL INTAKE
|
|
|
10' from property line
|
2009 IMC 401.4(1)
|
|
10' from center line of public way
|
2009 IMC 401.4(1)
|
|
10' from Xcel transformer
|
Xcel Blue book.
|
|
10' from building environmental exhaust
|
2009 IMC 501.2.1(3)
|
|
10' from plumbing vents or 3' below if <10'
|
2009 IMC 401.4(3)
|
|
GENERAL EXHAUST
|
|
|
3' from property lines, openigs into buildings
|
2009 IMC 501.2.1(3)
|
|
10' from mechanical air inlets
|
2009 IMC 501.2.1(3)
|
|
Type I Commercial Hood Exhaust
|
See figure 506.3.10, 10.1(1) and 10.1(2) for summary
|
|
Type II Commercial Hood
|
2009 IMC 506.4.2 & 501.2.1(3) Environmental Air.
|
|
Machinery eqmt rm
|
2009 IMC 918.6(3)
|
|
Kitchen
|
2009 IMC 918.6(5)
|
|
Exception: > than 10' from cooking appl.
|
Exception 2009 IMC 918.6(5)
|
|
Closet, bathroom, garage, boiler/furnace room, unconditioned attic/crawlspace
|
2009 IMC 918.6(5)
|
|
Not required - If not required then must comply with IBC 713.2 through 713.3.3
|
|
|
Required Ratings of Fire Dampers
|
See 2009 IBC Table 716.3.2.1
|
|
Fire Walls fire damper required
|
2009 IBC 716.5.1
|
|
Smoke damper required only serves horizontal exit
|
2009 IBC 716.5.1.1
|
|
Fire Barriers
|
2009 IBC 716.5.2
|
|
Fire Damper Required
|
|
|
Exception - Not required if all below apply:
|
building sprinklered, wall rating <1hr, Not grp H, 26ga duct, ducted sa,ra
|
|
Smoke damper required only if fire wall serves horizontal exit
|
2009 IBC 716.5.2.1
|
|
Shaft Enclosures
|
2009 IBC 716.5.3
|
|
Fire/Smoke Damper required at all penetrations
|
2009 IBC 716.5.3
|
|
Fire Partitions
|
|
|
Fire Damper Required
|
2009 IBC 716.5.4
|
|
Exception - Not required if all below apply:
|
Bldg fully sprinkered, fire caulked per 713
|
|
Corridors
|
|
|
Smoke damper required.
|
2009 IBC 716.5.4.1
|
|
Exception - Not required if all below apply:
|
No openings in corridor, duct >.019
|
|
Show Working Space around all HVAC equipment, panels and etc on plans with hatched area.
|
2009 IMC 306.1 & Manuf. Installation instructions.
|
|
Permanent ladder required if roof over 16'.
|
2009 IMC 306.5
|
|
Level walking surface if roof pitch is over 4/12.
|
2009 IMC 306.5
|
|
Guard rails req'd if equip < 10' from edge of roof or 30" drop in elevation. Note this applies to RTU, Fans, roof hatches. Extend 42" high guard, 30" past equipment. Prevent 21" dia sphere.
|
2009 IMC 304.11
|
|
Maintenance recptacle, GFI, Same roof level and within 25' of equipment.
|
2009 IMC 306.5.2 in accordance with 2011 NEC 210.8(B)(3) & 210.63
|
|
Maintenance platforms req'd if slope of roof is >3/12. If platform is over 30" above roof, a guard rail is required.
|
2009 IMC 306.5.1
|
|
Atmospheric vented appliance shall not be in:bedroom, bathroom, toilet room, storage (except sealed combustion)
|
2009 IMC 303.3
|
|
Appliance in Public garages suspended from the ceiling where vehicles can pass under shall be min 8' or 1' higher than the vehicle entry door, which ever is greater.
|
2009 IMC 304.6
|
|
Appliance in Private garages suspended from the ceiling where vehicles can pass under shall be min 6' or 1' higher than the vehicle entry door, which ever is greater.
|
2009 IMC 304.7
|
|
Room Access Doors - 36" wide X 80" tall.
|
2009 IMC 306.2
|